Homepage | Set Home | Add to Favorites
Member

Taizhou Xinkong Automation Technology Co., Ltd


Products
  • No Category
Search
 

Friends links

6ES7307-1BA01-0AA0
Click image to view full size image
Product: Views:1276ES7307-1BA01-0AA0 
Unit price: Negotiable
MOQ:
Quantity:
Delivery date: Since the payment date Days delivery
Valid until: Long-term effective
Last updated: 2020-07-09 06:14
  Inquiry
Details

SIMATIC S7-300 Regulated power supply PS307 input: 120/230 V AC, output: 24 V DC/2 A


Technical data

Input

Input
Note

1-phase AC

Automatic range selection

Supply voltage
1 at AC Rated value
2 at AC Rated value

120 V

230 V

Input voltage
1 at AC
2 at AC

85 ... 132 V
170 ... 264 V

Wide-range input

No

Overvoltage resistance

2.3 × Vin rated, 1.3 ms

Mains buffering

at Vin = 93/187 V

Rated line frequency 1

50 Hz

Rated line frequency 2

60 Hz

Rated line range

47 ... 63 Hz

Input current
at rated input voltage 120 V
at rated input voltage 230 V

0.9 A

0.5 A

Switch-on current limiting (+25 °C), max.

22 A

Duration of inrush current limiting at 25 °Cmaximum

3 ms

I²t, max.

1 A²·s

Built-in incoming fuse

T 1.6 A/250 V (not accessible)

Protection in the mains power input (IEC 898)

Recommended miniature circuit breaker: 3 A characteristic C


Output

Output

Controlled, isolated DC voltage

Rated voltage Vout DC

24 V

Total tolerance, static ±

3 %

Static mains compensation, approx.

0.1 %

Static load balancing, approx.

0.2 %

Residual ripple peak-peak, max.

50 mV

Residual ripple peak-peak, typ.

5 mV

Spikes peak-peak, max. (bandwidth: 20 MHz)

150 mV

Spikes peak-peak, typ. (bandwidth: 20 MHz)

20 mV

Product function Output voltage adjustable

No

Output voltage setting

-

Status display

Green LED for 24 V OK

On/off behavior

No overshoot of Vout (soft start)

Startup delay, max.

2 s

Voltage rise, typ.

10 ms

Rated current value Iout rated

2 A

Current range

0 ... 2 A

Supplied active power typical

48 W

Short-term overload current
on short-circuiting during the start-up typical
at short-circuit during operation typical

9 A

9 A

Duration of overloading capability for excess current
on short-circuiting during the start-up
at short-circuit during operation

90 ms

90 ms

Parallel switching for enhanced performance

Yes

Numbers of parallel switchable units for enhanced performance

2


Efficiency

Efficiency at Vout rated, Iout rated, approx.

84 %

Power loss at Vout rated, Iout rated, approx.

9 W


Closed-loop control

Dynamic mains compensation (Vin rated ±15 %), max.

0.1 %

Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.

0.8 %

Load step setting time 50 to 100%, typ.

0.5 ms

Load step setting time 100 to 50%, typ.

0.5 ms

Setting time maximum

1 ms


Protection and monitoring

Output overvoltage protection

Additional control loop, shutdown at < 28.8 V, automatic restart

Current limitation

2.2 ... 2.6 A

Property of the output Short-circuit proof

Yes

Short-circuit protection

Electronic shutdown, automatic restart

Enduring short circuit current RMS value
maximum

2 A

Overload/short-circuit indicator

-


Safety

Primary/secondary isolation

Yes

Galvanic isolation

Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

Protection class

Class I

Leakage current
maximum
typical

3.5 mA

0.5 mA

Degree of protection (EN 60529)

IP20


Approvals

CE mark

Yes

UL/cUL (CSA) approval

cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

Explosion protection

ATEX (EX) II 3G Ex nA II T4; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455

FM approval

Class I, Div. 2, Group ABCD, T4

CB approval

No

Marine approval

In S7-300 system


EMC

Emitted interference

EN 55022 Class B

Supply harmonics limitation

not applicable

Noise immunity

EN 61000-6-2


Environmental conditions

Ambient temperature
during operation
— Note
during transport
during storage

0 ... 60 °C
with natural convection
-40 ... +85 °C
-40 ... +85 °C

Humidity class according to EN 60721

Climate class 3K3, 5 … 95% no condensation


Mechanics

Connection technology

screw-type terminals

Connections
Supply input
Output
Auxiliary

L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
-

Width of the enclosure

40 mm

Height of the enclosure

125 mm

Depth of the enclosure

120 mm

Required spacing
top
bottom
left
right

40 mm

40 mm
0 mm
0 mm

Weight, approx.

0.4 kg

Product feature of the enclosure housing for side-by-side mounting

Yes

Installation

Can be mounted onto S7 rail

Mechanical accessories

Mounting adapter for standard mounting rail (6EP1971-1BA00)

MTBF at 40 °C

2 320 078 h

Other information

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

http://www.plcchinasupplier.com/

Inquiry